Part 04 ·
In a closed bedroom it is
3,700 ppm by morning.
In a larger one, 1,400.
In a closed bedroom of eleven square metres the concentration of carbon dioxide reaches 3,700 ppm by morning. In a thirty-metre bedroom, 1,400. Same night, same people, same airtightness of the windows. The difference is made by the volume of air alone.
The fourth part of the series on the plan study. This one is about the eight hours barely mentioned in design, although they take up a third of a life: sleep.
How much carbon dioxide builds up overnight
Two people sleeping in a closed room exhale, over eight hours, enough carbon dioxide that with the typical airtightness of today's windows it has nowhere to go. We calculated this for bedrooms of different volume, from 28 to 92 m³.
bedroom 11 m², 28 m³ bedroom 16 m², 49 m³ bedroom 30 m², 92 m³ ventilation 30 m³/h per person
start of sleep2 h4 h6 h8 h
Vertical axis from zero to 3,800 ppm. The values after eight hours come from the study; the course over time we took as linear. Outside air 420 ppm.
After eight hours it comes out between 1,400 and 3,700 ppm, depending on the size of the room. The worst is in the smallest bedrooms, especially where a small floor area is combined with a low clear height: at 11 square metres and 2.5 metres of height the volume is 28 m³ and by morning it is 3,700 ppm.
A large bedroom works as a buffer. Thirty square metres at a height of over three metres is 92 m³ and 1,400 ppm on the same night. That is, in our view, the most interesting argument for a larger bedroom we found in the whole study, and quite different from the one usually used to defend it.
Mechanical ventilation settles this regardless of floor area. At 30 m³ an hour per person the concentration stabilises around 920 ppm and stops depending on how large the room is.
Does it matter
It does, and that is measured rather than assumed. Danish studies at the Technical University of Denmark compared sleep with the window closed and open: the average overnight concentration was 2,585 ppm against 660 ppm. With better ventilation, sleep efficiency and next-day test results both improved.
One detail from those studies matters more for design than the result itself. In a study of twenty-nine bedrooms, only an open window improved sleep and performance. Opening the door to the corridor alone lowered the carbon dioxide concentration but did not improve sleep. So a room does not exchange air with the rest of the house the way we imagine when we draw an open layout.
And this is where the conflict starts
The answer “sleep with the window ajar” only works on a quiet plot. The World Health Organization recommends below 30 decibels in a bedroom at night. A window left ajar damps outside noise by some 15 decibels.
The WHO recommendation for a bedroom at night is below 30 dB. The 2018 guidelines for Europe give below 45 dB outside at night for road traffic.
Above roughly 45 decibels outside, a bedroom cannot have both fresh air and quiet with the window ajar. Then there is no choice: mechanical ventilation with the window closed is needed.
That is a concrete question to ask on the first visit to the plot, before a plan exists. Not “are we doing heat recovery”, but “how many decibels is it here at night”, because that decides whether the bedrooms can face the road.
Seven months with the window shut
In the Polish climate, bedroom windows are closed at night from roughly October to April. That is seven months of the year in which, without mechanical ventilation, the carbon dioxide concentration in a bedroom with a volume below about 58 m³ passes 2,000 ppm.
In practice that means heat recovery in a premium house is not an addition to comfort or a way of managing bills. It is the only solution to a problem that occurs every night for more than half the year.
Summer: the same bedroom, the opposite problem
In winter a bedroom has too little air. In summer it has too much heat, and from the same window that is an asset for the rest of the year. Harvard studied fifty older people across eleven thousand nights in their own homes: the best sleep came at twenty to twenty-five degrees, and as the temperature rose from twenty-five to thirty, sleep efficiency fell by five to ten per cent.
Unshaded glass, solar factor 0.5, direct radiation only. East and west get the most, about 1.9 kWh per square metre of glass a day; south less, because the sun stands high; north the least.
West is the worst direction here, and not because it gets the most heat in total but because it gets it in the afternoon, just before sleep. A bedroom with a floor-level window facing west collects about fifteen kilowatt-hours a day in summer, two and a half times more than the same bedroom with a three-metre window.
External shading cuts that roughly in half. An internal curtain does not, because by then the heat is already in the room. That is a decision from the elevation stage, not the finishing stage, and that is why it belongs in this study rather than in a conversation about curtains.
Bedroom volume, six results
A range “from fourteen hundred to thirty-seven hundred” says little until you see what it depends on. It depends almost entirely on volume, and volume on floor area and clear height.
| Bedroom | Volume | After eight hours, window closed | With supply air of 60 m³/h |
|---|---|---|---|
| 11 m², 2.5 m high | 28 m³ | 3,694 ppm | 920 ppm |
| 13.4 m², 2.9 m | 39 m³ | 2,761 ppm | 920 ppm |
| 16.4 m², 3.0 m | 49 m³ | 2,269 ppm | 920 ppm |
| 20.7 m², 2.9 m | 60 m³ | 1,936 ppm | 920 ppm |
| 26.4 m², 2.9 m | 77 m³ | 1,610 ppm | 919 ppm |
| 29.8 m², 3.1 m | 92 m³ | 1,405 ppm | 917 ppm |
Model: two people sleeping, emission of 15 litres of carbon dioxide an hour per person, outside air 420 ppm. Volume from floor area and clear height.
A bedroom of 28 m³ ends the night at a value two and a half times higher than a bedroom of 92 m³, in an identical scenario. A large bedroom simply buffers.
More important is that in the right-hand column floor area stops mattering. With thirty cubic metres of supply air per person, each of these bedrooms stabilises at around nine hundred and twenty ppm, from the smallest to the largest. Volume is a buffer that only delays. Ventilation is the solution.
That is also the answer to whether you can sleep well in a small bedroom. You can, provided it has something to breathe. That is why we design supply air into every bedroom.
What stands next to the bedroom
A washing machine on spin is sixty-odd decibels for a quarter of an hour, and the World Health Organization threshold for a bedroom at night is thirty. We design the laundry away from the bedroom wall, or separate it with a dressing room.
The bed on the plan
A plan shows walls and windows, not what you look at while lying down. We draw the bed together with the plan and leave 75 cm on both sides, the dimension Neufert gives as a working one. We look at the windows too: in June the sun is on a bed by a west window even after eight in the evening, as the part about sunlight shows.
What an open ground floor sounds like
We calculated the reverberation time of an open living zone, using Sabine's formula, for three variants of finish. The regulations give no value for houses; for comparison, no more than 0.6 seconds is assumed for classrooms.
A living zone of about 105 m² at a height of 3.0–3.1 m. Double-height spaces lengthen reverberation further.
Two point three seconds is a value from a sports hall, not a house. With a finish like that, a conversation at a table for twelve stops being a conversation, and the television can be heard upstairs. Furniture and textiles pull it down to a second, but a second is not comfortable for talking either. That is why we design the acoustics of the living zone together with the architecture.
On top of that there is the kitchen. An open kitchen joins several dozen square metres of space, and in a large house more than two hundred. Research from Lawrence Berkeley National Laboratory shows that good extract hoods capture over 90 per cent of pollutants from the back burners, but only 46 to 78 per cent from the front ones. Everything the hood does not catch spreads through that whole space, and through a double-height living room to the floor above as well.
And one more thing from the same research, worth knowing before choosing equipment: the hood with the highest efficiency for the front burners was at the same time too loud to talk next to. With the long reverberation of an open ground floor, that noise spreads across the whole level.
What this part does not cover
- The carbon dioxide model assumes two people, a sealed room and no exchange with the rest of the house. Real airtightness depends on the joinery and on whether the door has an undercut.
- The build-up over time we took as linear. The values after eight hours are from the study; the shape of the curve is a simplification.
- Reverberation is calculated with Sabine's formula for a rectangular box, without double-height spaces. It is an order-of-magnitude estimate, not a measurement.
- We did not measure noise on the plots. The values in the table are typical levels for a given type of road, not a measurement at a particular house.
What follows from this in design
The volume of a bedroom is a health parameter, not only a comfort one. Floor area times clear height decides what you are breathing by morning.
We measure the noise on a plot before we place the bedrooms. Above 45 decibels at night, a bedroom by a road needs mechanical ventilation, not thicker glass.
We design the acoustics of an open living zone together with the architecture. The difference between 2.3 and 0.6 seconds is the difference between a sports hall and a room.
Sources. Strøm-Tejsen P., Zukowska D., Wargocki P., Wyon D. (2016), The effects of bedroom air quality on sleep and next-day performance; Strøm-Tejsen et al. (2014), CO₂ controlled bedroom ventilation, DTU. Fan X. et al. (2022), The effects of bedroom window/door opening, Indoor Air. WHO: Night Noise Guidelines for Europe (2009) and Environmental Noise Guidelines for the European Region (2018). Lawrence Berkeley National Laboratory, the efficiency of kitchen extract hoods. House data: MOOMOO detached house plan study, final edition, October 2026, parts 12 and 13.
Licence. The figures and charts in this part are released under CC BY 4.0. They may be quoted, adapted and used commercially, crediting MOOMOO Architects as the source. Photographs and visualisations are not covered by the licence.
The whole study in one file
A hundred and thirty-five pages, twenty houses and apartments, fourteen parts and a hundred and eighteen drawings. Everything this series was built from, in full. The file is in Polish; the drawings and tables read without it, and an English edition is in preparation.
135pages 20houses 14parts 118drawings
Prefer to look first? The whole series is readable here, part by part, without signing up.
Compiled by: Łukasz Pastuszkaarchitect, co-founder, MOOMOO Architects